17th-Floor Cooling Tower Basin Restoration

Restoration of a leaking cooling tower basin 17 floors above street level using epoxy primer, one inch of high-density foam and a 100-mil polyurea liner.

Request a Quote (RFQ)
Services

Cooling Tower Solutions, Insulation & Spray Foam

Environment

High-rise commercial building

Location

Peoria, Illinois

Year

2026

Project field footage

Original field footage documenting the application.

High-density spray foam application
Tan polyurea liner application

A deteriorated cooling tower basin on the 17th floor of a Peoria, Illinois building had developed leaks that were allowing water to enter the residence below on the 16th floor. The project called for a seamless repair system that would insulate the basin and restore its water-retaining surface without replacing the entire assembly.

Logistics were a major part of the job. Mobilizing equipment and materials 17 stories above street level required planning around the building's existing access and the limited work area. A separate contractor completed abrasive blasting and substrate preparation before the coating and insulation work began.

Epoxy primer was applied to the prepared substrate, followed by one inch of NCFI high-density, nominal three-pound spray polyurethane roofing foam. The foam was selected to create an insulating layer and fill irregularities and cracks in the basin assembly. Over the foam, the system included approximately 100 mils of tan, pure aliphatic polyurea from Oak Ridge Foam & Coating Systems. This continuous protective lining was designed to seal the system and address water intrusion. The finished coating forms the exposed protective surface, while the foam provides the underlying thermal break.

The original photographs and field videos show the prepared basin, spray foam application and the finished tan liner. This project is a practical example of combining insulation and protective coating capabilities in a difficult high-rise environment. Substrate integrity and suitability of the entire lining system for the specific operating conditions remain essential considerations for cooling tower restoration.

Material technical references

NCFI publishes a nominal three-pound EnduraTech roofing foam reference with typical lab-reported R-value of 6.7 per inch and core density of 3.0 pcf. Exact installed product identifiers and suitability for this basin must be confirmed against the original project submittals.

Current manufacturer reference documents, not original job-specific product approval or installation records.

Project photography

10 actual field photos. Select a photograph to view it in full.

17th-Floor Cooling Tower Basin Restoration: project photograph 117th-Floor Cooling Tower Basin Restoration: project photograph 217th-Floor Cooling Tower Basin Restoration: project photograph 317th-Floor Cooling Tower Basin Restoration: project photograph 417th-Floor Cooling Tower Basin Restoration: project photograph 517th-Floor Cooling Tower Basin Restoration: project photograph 617th-Floor Cooling Tower Basin Restoration: project photograph 717th-Floor Cooling Tower Basin Restoration: project photograph 817th-Floor Cooling Tower Basin Restoration: project photograph 917th-Floor Cooling Tower Basin Restoration: project photograph 10